GSO-100-200 AIR COOLING OUT DOOR CABINET-ON GRID MACHINE
Product Introduction :
The air cooling outdoor cabinet-on grid machine integrates energy storage batteries, PCS, EMS, air conditioning and fire protection systems. It is a product specially launched for the application needs of small industrial and commercial, hospital buildings, and household energy storage peak-shaving and valley-filling applications.
Product Parameters
Model |
GSO-50-100-V GSO-100-200-V |
||
Rated power(kW) |
50 |
100 |
|
On grid parameter |
Maximum output power(kW) |
55 |
110 |
Rated AC voltage(V) |
AC |
400 |
|
AC voltage range(V) |
AC 400V(-20%~+15%) |
||
Rated AC frequency(Hz) |
50/60±2.5 |
||
Power factor |
-0.99~+0.99 |
||
THDI |
≤3%(Full loading) |
||
Charging and discharging conversion time(ms) |
<100 |
||
Isolation method |
None isolation |
||
Connect method |
Three phase four wire |
||
Off grid parameter |
Rated output voltage(V) |
AC 400±3% |
|
Rated output power(kW) |
100 |
||
Rated output frequency(Hz) |
50 |
/60 |
|
THDU |
≤3%(Linear load) |
||
Unbalanced load capacity |
100% |
||
Overload capacity |
1.1times long-term(45℃),1.2times 1min |
||
Charging and discharging conversion time(ms) |
<20 |
||
Battery parameter |
Battery configuration |
1P225S |
1P210S |
Battery cell type |
LFP 150Ah |
LFP 300Ah |
|
Nominal voltage(V) |
720 |
672 |
|
Operating voltage(V) |
652.5~798.75 |
609~745.5 |
|
Battery capacity(kWh) |
108 |
201 |
|
PV System efficiency |
Voltage range(V) |
500~620 |
500~580 |
Maximum input power(kW) |
55(10min) |
110(10min) |
|
Rated current on low voltage side(A) |
≤100 |
≤200 |
|
Maximum efficiency |
≥99% |
||
|
|||
PCS maximum efficiency |
|
||
System maximum efficiency |
>90% |
||
Charging and discharging rate |
≤0.5C |
||
Protection |
AC input |
Yes |
|
PCS AC protection |
Yes |
||
AC output protection |
Yes |
||
Over voltage protection |
Yes |
||
Fire protection |
Aerosol / Perfluoro |
||
General parameter |
Dimension(D*W*H) |
1200*1300*2200 |
1200*1800*2200 |
Weight(t) |
1.9 |
3.2 |
|
Incoming line method |
Side connection |
||
Operating temperature range(℃) |
-20~50(De-rating power from 45) |
||
Temperature humidity(%RH) |
<95,Non-condensing |
||
Work Altitude |
5000(De-rating power from 2000) |
||
IP grade |
IP54(Key Device IP65) |
||
Cooling method |
Industrial air Conditioning(for battery )/ Forced air cooling( for electrical equipment) |
||
Communication |
Communication interfaces |
RS485/Ethernet |
|
Communication Rules |
RTU/MODBUS-TCP |